Energy and Sustainability

Steam Trap Survey Log Excel Template

Log every steam trap test, put a yearly cost on each failed trap from the surveyed loss or the DOE orifice table, and track repairs, open losses and the share of traps losing steam.

Free, and a plain .xlsx with no macros to enable. A CSV with live formulas and a printed how-to guide come with it.

Overview

This steam trap survey log is a working Excel workbook for maintenance, energy and utilities managers and steam technicians who test steam traps and need the result in money. It ships with four quarterly surveys of 60 traps at a fictional food plant, so the dashboard and charts are populated the moment you open it; replace the example rows with your own and everything recalculates.

Each row is one trap tested in one survey. A trap that is leaking or has failed open blows live steam into the condensate return for every hour its header is under pressure, so the workbook prices it the way the Steam Trap Loss and Steam Leak Cost calculators on this site do: steam loss in pounds an hour, times the header's pressurized hours, times the cost of 1,000 pounds of steam. When the survey gives no figure for a failed-open trap, it uses the U.S. Department of Energy's published discharge rate for the trap's orifice at its header pressure. Repairs close a finding, and a later test of the same tag replaces an earlier one, so an open loss is never counted twice.

In practice, log each survey as it is done and review the dashboard before the repair budget is set. The share of traps losing steam shows whether the program is working against the DOE's guide of under 5% for a regularly maintained system, the by-header and by-trap-type tables show where failures cluster, and the fix-first list puts the open losses in order of what they cost a year.

What this template includes

Suggested use case

Use it to run a steam trap survey program: log each survey, put the failed traps in money for the repair budget, see which headers and trap types fail most, and show the share of traps losing steam falling survey by survey.

How to use it

  1. On Setup, enter your plant name and currency, then your steam headers with their pressure, pressurized hours a year and steam cost per 1,000 lb, your trap types with a replacement cost, and your surveys.
  2. On Survey Log, add one row per trap tested: survey, date, tag, location, header, trap type, orifice and the condition found.
  3. For a leaking trap, type the loss the survey gave; for a failed-open trap, leave it blank to use the DOE table at 15, 100, 150 or 300 psig, or type a surveyed loss.
  4. Type the repair date when a trap is fixed, and fix anything the Check column flags.
  5. On the Dashboard, pick a survey (or leave it blank for the latest) and a header, then work down the list of open losses to fix first.

Frequently Asked Questions

How much does a failed steam trap cost?
Steam loss times the hours the line is pressurized times the cost of steam. In the U.S. Department of Energy's example, a 1/8-inch trap orifice stuck open on a 150 psig line loses 75.8 lb/h; at 8,760 hours and 10.00 per 1,000 lb that is 6,640 a year. In the example plant, the 15 traps found losing steam in the first survey cost 62,957 a year.
Where do the steam loss figures come from?
Type the loss your survey gave when you have one. For a failed-open trap without one, the workbook uses DOE Steam Tip Sheet #1's discharge rate for the orifice diameter at the header pressure, a table from the Boiler Efficiency Institute for steam discharging to atmosphere through an orifice with a discharge coefficient of 0.72. It covers 15, 100, 150 and 300 psig only and nothing is interpolated: at any other pressure, type the loss.
What share of steam traps should be failed?
The DOE's tip sheet says that in systems not maintained for 3 to 5 years, 15% to 30% of traps may have failed, and that with a regular maintenance program leaking traps should be under 5% of the population. The 5% is the default target on Setup. The example plant goes from 25.9% of tested traps losing steam in its first survey to 5.0% in its fourth.
How often should steam traps be tested?
DOE Steam Tip Sheet #1 suggests weekly to monthly for traps on high-pressure lines (150 psig and above), monthly to quarterly for medium pressure (30 to 150 psig) and annually for low pressure (below 30 psig). The survey planner gives the time a survey takes: 60 traps at 0.2 traps a minute with a 25% allowance is 375 person-minutes, about 3.1 hours for two surveyors.
What steam cost should I use?
The marginal cost of 1,000 lb of steam on each header: fuel, water, treatment and pumping. The Setup helper works out the fuel part by DOE Steam Tip Sheet #15's method: fuel price times the heat to make a pound of steam, divided by the combustion efficiency. In the tip sheet's example, natural gas at 8.00 per MMBtu, 1,006 Btu/lb and 85.7% efficiency is 9.39 per 1,000 lb.